Print this page Download this page as a pdf
Sprinklers » Residential » Residential Sprinklers

A-3 Automatic Sprinklers Model GL3010

Automatic Spinklers Model GL3010 Pendent Recessed Pendent

Description and OperationSprinklers

The Globe Model GL3010 Residential Sprinkler has a low profile yet durable design, which utilizes a 3mm frangible glass ampule as the thermosensitive element. It features economy, aesthetics and low flow.

The combination of the 3mm frangible glass ampule and specially designed deflector makes the Model GL3010 Residential Sprinkler the ultimate in life safety and fire control. This Globe Pendent and Recessed Pendent Residential Sprinkler has met the strict requirements of Underwriters Laboratories Inc. as described in the UL Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction.

The heart of Globe's Model GL3010 sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.

Technical Data

  • Temperature Rating - 155°F (68°C)
  • Water Working Pressure Rating - 175 psi (12 Bars).
  • Factory tested hydrostatically to 500 psi (34 Bars).
  • Maximum low temperature glass bulb rating is
    -67°F (-55°C).
  • Frame - bronze
  • Deflector - brass
  • Screw - brass
  • Bulb seat - copper
  • Spring - nickel alloy
  • Seal - teflon
  • Bulb - glass with alcohol based solution, 3mm size.
  • Escutcheon Assembly - steel

Sprinkler Temperature Rating/Classification and Color Coding

Classification Available Sprinkler Temperatures Bulb Color N.F.P.A. Maximum Ceiling Temperature
Ordinary 155°F 68°C Red 100°F 38°C

Specifications and Approvals

Sin Model K Factor Thread Size Length Finishes 155°F
68°C
NYC-DOB
MEA 101-92-E
GL3010 3.0
(42 metric)
1/2" NPT 2 1/2" (6.4 cm) Factory Bronze
Satin Chrome1
Bright Chrome
White Polyester2
Black Polyester2
Lead Coated1
Note:
  • Metric conversions are approximate.
  • 1Finishes available on special order.
  • 2C-U.L. Listed Corrosion Resistant - Polyester must be specified on order.

Cross Section

Gl5635

Click image above for a detailed view of this product.

Installation Data for Flat and Sloped Ceilings**

Pendent and Recessed Pendent

Maximum Area of Coverage Minimum Water Discharge &
Pressures Needed Per Sprinkler*
12' x 12' 8 G.P.M. - 7.1 P.S.I.
14' x 14' 10 G.P.M. - 11.1 P.S.I.

*When these sprinklers are used in NFPA 13 systems, a 0.1 design density minimum shall be utilized.

**Refer to page 2 of the Globe Residential Sprinkler Installation Guide for NFPA 13D and 13R requirements.

Ordering Information

When ordering please specify the following.

  • Quantity
  • Model Number
  • Style
  • Orifice
  • Temperature
  • Finishes desired
  • Quantity - Wrenches - P/N 325390
  • Quantity - Recessed Wrenches - P/N 325391
  • Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)

Related Products

  • No related products found

Globe Product Warranty

Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

Bulletin: BULLETIN GL 3010   Last Revised: September 2011   Revision: 1

site by visual chutzpah