A-12 Millennium Flush Pendent Sprinkler - GL4248
Automatic Sprinklers Millennium™ GL4248 Flush Pendent
Description and Operation
The Globe Millennium™ Residential Flush Pendent Sprinkler is a low profile, aesthetically pleasing, flush mounted sprinkler that utilizes a 2.5mm frangible glass ampule as the thermosensitive element.
The combination of the 2.5mm frangible glass ampule and specially designed deflector make the Millennium™ Residential Sprinkler the ultimate in life safety and fire control. The sprinklers have met the strict requirements of Underwriters Laboratories Inc. as described in the Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be installed in accordance with the appropriate National Fire Protection Association Standard NFPA 13, 13D or 13R.
The heart of Globe's Millennium™ Sprinkler actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, when the internal pressure exceeds the strength of the glass ampule, the ampule ruptures. The levers that had been held in position by the bulb now collapse inward allowing the deflector and Teflon coated belleville washer seal to move downward to the full operated position. This results in water discharge that is distributed in an approved pattern.
Technical Data
- Temperature Rating - 155°F (68°C)
- Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Body - bronze
- Deflector - bronze
- Orifice Insert - brass
- Splitter - brass
- Belleville Spring - beryllium nickel
- Teflon gasket - teflon
- Drop pin - bronze
- Lever arm - bronze
- Load bar - bronze
- Ceiling cover - brass
- Load screw - stainless steel
- Bulb - glass with alcohol based solution, 2.5mm size
- Escutcheon - steel
- Dust cover - nylon
- Pin cover - nylon
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
| Intermediate | 175°F | 79°C | Yellow | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 1/2" NPT | 2 1/2" (6.4 cm) |
Bright Chrome White Polyester Black Polyester1 |
||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 155°F 68°C | cULus |
|---|---|---|---|---|
| Flush Pendent | GL4248 | 4.1 | • | • |
Cross Section
Click image above for a detailed view of this product.
Installation Data
Flush Pendent
| Model | Maximum Area of Coverage | Minimum Water Discharge & Pressures Needed (for up to 2/12 slope) | Minimum Water Discharge & Pressures Needed (for up to 8/12 slope) |
|---|---|---|---|
| GL4248 | 12' x 12' | 11 G.P.M. - 7.2 P.S.I. |
22 G.P.M. - 28.8 P.S.I. |
| 14' x 14' | 11 G.P.M. - 7.2 P.S.I. | 22 G.P.M. - 28.8 P.S.I. | |
| 16' x 16' | 13 G.P.M. - 10 P.S.I. | 22 G.P.M. - 28.8 P.S.I. | |
| 18' x 18' | 17 G.P.M. - 17.2 P.S.I. | 22 G.P.M. - 28.8 P.S.I. | |
| 20' x 20' | 20 G.P.M. - 23.8 P.S.I. | 22 G.P.M. - 28.8 P.S.I. |
*When these sprinklers are used in NFPA 13 Systems, a 0.1 design density minimums shall be utilized.
Minimum 9' sprinkler spacing.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Millennium Wrenches - P/N 332334
Product Related Documents
Related Products
Globe Product Warranty
Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).
Bulletin: GL4248 Last Revised: July 2005 Revision: 5