Print this page Download this page as a pdf
Sprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Pendent

A-41 Extended Coverage Light Hazard Pendent Sprinkler - GL8109

Extended Coverage Light Hazard Automatic Sprinklers Model GL8109 Pendent

Description and Operation

Quick Response

The Globe Quick Response Model GL8109 Extended Coverage Pendent Sprinkler for Light Hazard occupancies is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While this Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard light hazard extended coverage pendent sprinklers are specified; but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction, in accordance with their listings and in accordance with NFPA 13.

The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.

Technical Data

  • Temperature Ratings -
    135°F (57°C)
    155°F (68°C)
    175°F (79°C)
    200°F (93°C)
  • Water Working Pressure Rating -
    175 psi (12 Bars)
  • Factory tested hydrostatically to 500 psi (34 Bars)
  • Maximum low temperature glass bulb rating is
    -67°F (-55°C)
  • Frame - bronze
  • Deflector - brass
  • Screw - brass
  • Bulb seat - copper
  • Spring - nickel alloy
  • Seal - teflon
  • Bulb - glass with alcohol based solution, 3mm size
  • Upper Escutcheon Assembly - steel

Sprinkler Temperature Rating/Classification and Color Coding

ClassificationAvailable Sprinkler TemperaturesBulb ColorN.F.P.A. Maximum Ceiling Temperature
Ordinary 135°F/155°F 57°C/68°C Orange/Red 100°F 38°C
Intermediate 175°F/200°F 79°C/93°C Yellow/Green 150°F 66°C

Specifications

Nominal 'K' FactorThread SizeLengthFinishes
8.1 (116 metric) 3/4" NPT 3" (7.6 cm) Factory Bronze
Satin Chrome1
Bright Chrome
White Polyester2
Black Polyester2
Lead Coated1
Note:
  • Metric conversions are approximate.
  • 1Finishes available on special order.
  • 2Available as cULus listed corrosion resistant when specified on order.

Approvals

StyleSin ModelK Factor135°F
(57°C)
155°F
(68°C)
175°F
(79°C)
200°F
(93°C)
cULus
Pendent GL8109 8.1

U.L. Listing Design - Use Requirements For Light Hazards Only

Sin ModelStyleTempArea of Coverage
MIN. PRESSURE
P.S.I.
Flow in
G.P.M.
GL8109 Standard
&
Recessed
135°F / 57°C
155°F / 68°C
175°F / 79°C
200°F / 93°C
16' x 16' 10.3 26
18' x 18' 16.6 33
135°F / 57°C 20' x 20' 24.4 40
Note: Due to height spray pattern created by this sprinkler, there must be a minimum spacing of 8'-0" between sprinklers to eliminate the risk of cold soldering.

Cross Section

larger image

Click image above for a detailed view of this product

Ordering Information

When ordering please specify the following.

  • Quantity
  • Model Number
  • Style
  • Orifice
  • Temperature
  • Finishes desired
  • Quantity - Wrenches - P/N 312366
  • Quantity - Recessed Wrenches - P/N 325401, Rev. D
  • Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)

Product Related Documents

Related Products

Globe Product Warranty

Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

Bulletin: GL8109   Last Revised: July 2005   Revision: 5