Dry Sprinklers » Dry Type Horizontal Sidewall
A-93 Dry Type Horizontal Sidewall Sprinkler
GL Series Dry Type Horizontal Sidewall Recessed Horizontal Sidewall
Description and Operation
The Globe GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples.
The Globe GL Series Dry Type Horizontal Sidewall Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is -67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with glycerin solution, 5mm
- Orifice insert - brass
3/4" or 1" NPT - Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable FM Variable to |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester Black Polyester Lead Coated1 Wax Coated1 Wax Over Lead1 |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order
- Wax Coating cULus listed up to 200°F - cULus listed corrosion resistant: Polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | *FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Horizontal Sidewall |
GL5685a | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5686a | 5.6 | 3/4" NPT | • | • | • | • | • | • | – | • | |
| GL8185b | 8.1 | 1" NPT | • | • | • | • | • | • | – | • | |
| Recessed Horizontal Sidewall |
GL5685a | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5686a | 5.6 | 3/4" NPT | • | • | • | • | • | • | – | • | |
| GL8185b | 8.1 | 1" NPT | • | • | • | • | • | • | – | • |
Note:
- aListed for light hazard only with deflector from 4" to 12" below the ceiling.
- bListed for light and ordinary harzard with deflector from 4" to 12" below the ceiling.
- * Dry Horizontal Sidewall - FM Approved 155°F, 200°F, and 286°F only.
- * Dry Recessed Horizontal Sidewall - FM Approved 155°F and 200°F only.
Cross Sections

Important Installation Data
Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- Escutcheon desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Related Products
Globe Product Warranty
Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).
Bulletin: GL5685 Last Revised: August 2010 Revision: 14