Accelerator and Anti-Flooding Device Model C

Description and Operation

Globe's Model C Accelerator is a precision made device used to reduce the time lag normally associated with the opening of a Dry Pipe Valve after one or more system sprinklers have operated. In essence, the Model C Accelerator "accelerates" the opening of the Dry Pipe Valve resulting in faster water discharge from the opened sprinkler(s).

The Model C Accelerator basically monitors the air pressure in a Dry Pipe System. If a rapid loss of system air pressure occurs, as would with the opening of one or more sprinklers, the accelerator senses this loss and immediately sends pressurized air to the intermediate chamber of the Dry Pipe Valve upsetting the pressure differential and causing it to operate instantly.

Globe incorporates the use of its Model C Anti-Flooding Device to help ensure the proper operation of the Model C Accelerator by preventing most water-borne foreign objects from entering the Accelerator. Such objects could cause clogging of the Accelerator and hinder its proper operation. Because of its importance, the Model C Anti-Flooding Device is always included with orders for the Model C Accelerator and should always be properly installed. Accelerators are precision made devices, however, and must be kept clean of foreign matter. A thorough cleaning after use is recommended.

After the Accelerator has operated, the pressurized air in the Accelerator Body and its associated piping is discharged to the Model C Anti-Flooding Device's lower inlet stopping any flow through the piping leading to the Accelerator. This occurs very quickly and always before water reaches the Anti-Flooding Device.

Approvals

  • cULus Listed
  • FM Approved
  • N.Y.C. - D.O.B MEA 353-91-M

Technical Data

  • Water Working Pressure Rating - 175 psi (1207 kPa)

Cross Sections

Accelerator

Click image above for a detailed view of this product

ItemDescriptionMat'lP/N ItemDescriptionMat'lP/N
1 Upper Chamber Bronze 300401   9 Restricted Orifice Pin Monel 300411
2 Lower Chamber and Valve Seat Assembly Bronze 300402   10 Valve Disc and Disc Retainer Assembly Neoprene/Brass 300412
3 Pressure Plate Brass 300405   11 Retaining Screw Bronze 300415
4 Diaphragm Plate Brass 300406   12 Spring Retainer Disc Brass 300416
5 Nut Bronze 300407   13 Gasket E.P.D.M. 300417
6 Gasket E.P.D.M. 300408   14 Spring Bronze 300418
*7 Clamping Ring Brass 300409   15 Plug Brass 300419
*8 Diaphragm Neoprene 300410          

*323489 Accelerator Clamping Ring Wrench (Item #7) for use when replacing the Diaphram Item #8.

Refer to Globe’s Dry Pipe Valve Installation and Maintenance Guide (Bulletin D.P.V.I.M.) for trim set-up.Anti-Flooding Device

Click image for a detailed view of this product

ItemDescriptionMat'lP/N
1 Top Brass 323334
2 Body Brass 323333
3 Diaphragm E.P.D.M 323335
4 Spring Stainless Steel 323336
5 Screw Steel 323337

Ordering Information

When ordering please specify the following.

  • Quantity
  • Model Number
  • Size
  • Untrimmed or Factory Trimmed and Leak Tested Hydrostatically.

Product Related Documents

Related Products

  • No related products found

Globe Product Warranty

Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

Bulletin: AAFD   Last Revised: June 2002   Revision: 3

site by visual chutzpah