Print this page Download this page as a pdf
Valves & Accessories » System Sensor

WFD Series Waterflow Detector

WFD Series Waterflow Detector

Product Overview

WFD Series Waterflow Detector

New WFD30-2 models install in 2” hole sizes.

UL models are NEMA 4 rated

Sealed retard mechanism assures that the retard is not contaminated by dust and dirt when the cover is removed

Visual switch activation permits installer to accurately set retard under noisy conditions

Rugged, dual SPDT switches are enclosed in a durable terminal block

Accommodates up to 12 AWG wire

100% synchronization activates both alarm panel and local bell simultaneously

System Sensor’s WFD series is compatible with schedule 10 through 40 steel pipe, sizes 2” through 8”, and can be mounted in a vertical or horizontal position.

Robust Construction. The WFD series consists of a rugged, NEMA 4 rated enclosure. Designed for both indoor and outdoor use, the WFD series operates across a wide temperature range, from 32°F to 120°F.

Reliable Performance. UL listed models are equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to assure reliable performance.

False Alarm Immunity. The WFD series incorporates a mechanical retard feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the sprinkler system. In addition, the mechanical retard’s unique sealed design is immune to dust and other contaminants.

Simplified Operation. The WFD series is designed to simplify installation. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field-replaceable.

Specifications

Engineering Specifications

ApprovalsVane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6” from any fittings which may change water direction, flow rate, or pipe diameter or no closer than 24” from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi for 2” - 8” pipes. The detector shall respond to waterflow in the specified direction after a preset time delay which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or outdoor use.

Standard Specifications
Static Pressure Rating
450 PSI
Triggering Threshold Bandwidth
(Flow Rate)
4-10 GPM
Maximum Surge
18 Feet Per Second (FPS)
Compatible Pipe:
Steel water pipe, schedule 10 through 40
Contact Ratings
Two sets of SPDT (Form C)
10.0 A, 1/2 HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Conduit Entrances
Two openings for 1/2” conduit. One open, one knock-out type
Operating Temperature Range
32ºF to 120ºF (0ºC to 49ºC)
Enclosure Rating*
NEMA 4 - suitable for indoor/outdoor use
Cover Tamper Switch
Standard with ULC models
Optional for UL models, part no. 546-7000
Shipping Weight
WFD20: 4.2 lbs., WFD25: 4.3 lbs., WFD30: 4.5 lbs., WFD30-2: 4.5 lbs., WFD35: 4.7 lbs., WFD40: 5.2 lbs., WFD50: 6.3 lbs. WFD60: 6.8 lbs., WFD80: 7.5 lbs.
Service Use
Automatic Sprinkler: NFPA-13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA-72
Warranty
3 Years
U.S. Patent Numbers
3,845,259    4,782,333    5,213,205

Cross Section

Overall Dimensions Installed:

Click image above for a detailed view of this product

Ordering Information

Part Number Description
A3008-00 Retard mechanism
A77-01-02 Terminal block
546-7000 Tamper proof switch kit
546-7000 Tamer proof wrench for cover
WFDN4 Gasket kit

UL Model
Numbers
ULC/Canadian
Model Numbers
Pipe Size Hole Size
WFD20 WFD20A 2" 1¼"
WFD25 WFD25A 2½" 1¼"
WFD30 WFD30A 3" 1¼"
WFD30-2* WFD30-2A 3" 2"
WFD35 WFD35A 3½" 1¼"
WFD40 WFD40A 4" 2"
WFD50 WFD50A 5" 2"
WFD60 WFD60A 6" 2"
WFD80 WFD80A 8" 2"
*UL listed only.
UL Models
ULC/Canadian Models  
Replacement Parts
WFD20 WFD20A   A3008-00 Retard Mechanism
WFD25 WFD25A
  A77-01-02 Terminal Block
WFD30 WFD30A   546-7000 Cover Tamper Switch Kit
WFD30-2 WFD30-2A   WFDW Cover Wrench
WFD35 WFD35A   WFDN4 Replacement gasket kit
WFD40 WFD40A      
WFD50 WFD50A      
WFD60 WFD60A      
WFD80 WFD80A      


Related Products

Globe Product Warranty

Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

Bulletin: A05-180-06   Last Revised: June 2000   Revision: 45