Valves & Accessories » System Sensor
WFD Series Waterflow Detector
WFD Series Waterflow Detector
Product Overview
New WFD30-2 models install in 2” hole sizes.
UL models are NEMA 4 rated
Sealed retard mechanism assures that the retard is not contaminated by dust and dirt when the cover is removed
Visual switch activation permits installer to accurately set retard under noisy conditions
Rugged, dual SPDT switches are enclosed in a durable terminal block
Accommodates up to 12 AWG wire
100% synchronization activates both alarm panel and local bell simultaneously
System Sensor’s WFD series is compatible with schedule 10 through 40 steel pipe, sizes 2” through 8”, and can be mounted in a vertical or horizontal position.
Robust Construction. The WFD series consists of a rugged, NEMA 4 rated enclosure. Designed for both indoor and outdoor use, the WFD series operates across a wide temperature range, from 32°F to 120°F.
Reliable Performance. UL listed models are equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to assure reliable performance.
False Alarm Immunity. The WFD series incorporates a mechanical retard feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the sprinkler system. In addition, the mechanical retard’s unique sealed design is immune to dust and other contaminants.
Simplified Operation. The WFD series is designed to simplify installation. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field-replaceable.
Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6” from any fittings which may change water direction, flow rate, or pipe diameter or no closer than 24” from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi for 2” - 8” pipes. The detector shall respond to waterflow in the specified direction after a preset time delay which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or outdoor use.
|
Standard Specifications
|
|
|---|---|
| Static Pressure Rating |
450 PSI
|
| Triggering Threshold Bandwidth (Flow Rate) |
4-10 GPM
|
| Maximum Surge |
18 Feet Per Second (FPS)
|
| Compatible Pipe: |
Steel water pipe, schedule 10 through 40
|
| Contact Ratings |
Two sets of SPDT (Form C)
10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC |
| Conduit Entrances |
Two openings for 1/2” conduit. One open, one knock-out type
|
| Operating Temperature Range |
32ºF to 120ºF (0ºC to 49ºC)
|
| Enclosure Rating* |
NEMA 4 - suitable for indoor/outdoor use
|
| Cover Tamper Switch |
Standard with ULC models
Optional for UL models, part no. 546-7000 |
| Shipping Weight |
WFD20: 4.2 lbs., WFD25: 4.3 lbs., WFD30: 4.5 lbs., WFD30-2: 4.5 lbs., WFD35: 4.7 lbs., WFD40: 5.2 lbs., WFD50: 6.3 lbs. WFD60: 6.8 lbs., WFD80: 7.5 lbs.
|
| Service Use |
Automatic Sprinkler: NFPA-13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA-72 |
| Warranty |
3 Years
|
| U.S. Patent Numbers |
3,845,259 4,782,333 5,213,205
|
Cross Section
Overall Dimensions Installed:
Click image above for a detailed view of this product
Ordering Information
| Part Number | Description |
|---|---|
| A3008-00 | Retard mechanism |
| A77-01-02 | Terminal block |
| 546-7000 | Tamper proof switch kit |
| 546-7000 | Tamer proof wrench for cover |
| WFDN4 | Gasket kit |
| UL Model Numbers | ULC/Canadian Model Numbers | Pipe Size | Hole Size |
|---|---|---|---|
| WFD20 | WFD20A | 2" | 1¼" |
| WFD25 | WFD25A | 2½" | 1¼" |
| WFD30 | WFD30A | 3" | 1¼" |
| WFD30-2* | WFD30-2A | 3" | 2" |
| WFD35 | WFD35A | 3½" | 1¼" |
| WFD40 | WFD40A | 4" | 2" |
| WFD50 | WFD50A | 5" | 2" |
| WFD60 | WFD60A | 6" | 2" |
| WFD80 | WFD80A | 8" | 2" |
*UL listed only.
|
UL Models
| ULC/Canadian Models |
Replacement Parts
|
||
|---|---|---|---|---|
| WFD20 | WFD20A | A3008-00 | Retard Mechanism | |
| WFD25 | WFD25A |
A77-01-02 | Terminal Block | |
| WFD30 | WFD30A | 546-7000 | Cover Tamper Switch Kit | |
| WFD30-2 | WFD30-2A | WFDW | Cover Wrench | |
| WFD35 | WFD35A | WFDN4 | Replacement gasket kit | |
| WFD40 | WFD40A | |||
| WFD50 | WFD50A | |||
| WFD60 | WFD60A | |||
| WFD80 | WFD80A | |||
Related Products
Globe Product Warranty
Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).
Bulletin: A05-180-06 Last Revised: June 2000 Revision: 45