1/2" Domed Plate Concealed Sidewall - Extended Coverage Quick Response | Series GL-QR/ECLH/DCSW Glass Bulb - 5.6 K-factor
Not all temperatures and configurations may carry all Listings and Approvals. See data sheet for conditions of specific Listings and Approvals.
temperature | 135, 155, 175 |
approvals | cULus, NYC |
SIN | GL5613 |
wrench | 329678 |
QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD AUTOMATIC SPRINKLERS GL5613 & GL8113 CONCEALED HORIZONTAL SIDEWALL
GFS-230_20200316CM (.pdf)
Download
|
Recessed Horizontal Sidewall Revit Files (.zip) | Download |
Sprinkler Globe Concealed Horizontal Sidewall GL ECHL QR Imp (.rfa) | Download |
Sprinkler Globe Concealed Horizontal Sidewall GL ECHL QR Metric (.rfa) | Download |
Glass Bulb – 5.6 and 8.0 K-factor Domed Plate Concealed Extended Coverage Quick Response Light Hazard Sidewall Sprinkler: Where quick response, extended coverage, light hazard low profile domed plate concealed sidewall sprinklers are specified they shall be of an all bronze frame construction with brass deflector. Sprinklers shall have a 3mm glass bulb thermally sensitive operating element, and rated for a working pressure of 175 psi. Sprinklers installed in areas with a finished ceiling shall have a factory finished 3-5/16” cover plate and shall be of an appropriate temperature classification for the hazard and offer up to 1/2” adjustment. Sprinklers shall be UL listed. Quick response, extended coverage, light hazard domed plate concealed sidewall sprinklers shall be of the GL-QR/ECLH/DCSW Series; as manufactured by Globe Fire Sprinkler Corporation.
WARNING: Cancer and Reproductive Harm – www.P65Warnings.ca.gov.